Law 14,300: What is it and how to calculate the simultaneity factor?

See an explanation of the impact of Fio B charges on energy bills
Canal Solar O que é e como calcular o fator de simultaneidade
Understand the impact of Wire B on photovoltaic systems. Photo: Sharles Andrade

With the entry into force of Law 14,300 in January 2023, new photovoltaic plant projects will no longer have the Fio B exemption.

Fio B corresponds to one of the installments that make up the TUSD (Distribution System Usage Tariff).

The value of Fio B is responsible for covering the operational costs of distribution and investor remuneration and will be charged for plants smaller than 500 kW in a staggered manner, starting from 15% in 2023 until reaching 90% in 2028.

From 2029 onwards, there is still no definition of what should happen, as the competent bodies have not yet provided information.

Experts have projected two scenarios as the most likely. In the first of them, 100% would be charged for Fio B from 2029 and in a more unfavorable scenario, the entire TUSD would be charged – which would imply, in addition to Fio B, other charges that make up this tariff.

Impact of Wire B on photovoltaic systems

To simplify for the reader the impact of Fio B charging on energy bills, we present a simple explanation for this understanding.

Basically, energy invoices for new projects filed after the entry into force of Law 14,300 (01/07/2022) will come with an amount charged relating to Wire B, which refers to the use of the distribution system.

The owner of the photovoltaic system will pay this fee only on the excess energy that is injected into the grid and subsequently compensated in its own consumer unit or in other units that receive the credits.

With this charge, the return on investments in photovoltaic projects will be directly related to the simultaneity between generation and consumption.

The higher the consumption when generating electrical energy from the photovoltaic system, the lower the injection into the distributor's network and consequently the lower the Wire B rate included in your energy bill.

Simply put, the greater the injection into the grid, the greater the amount charged in the tariff for using surplus energy credits.

Therefore, from now on it is important to know how to calculate the simultaneity factor, as this variable directly impacts the financial return time on the investment.

Greater concurrency represents greater project profitability and shorter return on investment time, while lower concurrency reduces profitability and increases payback time.

Generating units with little injection (little excess energy and high simultaneity between consumption and generation) will not be greatly affected by the new rules. On the other hand, units with low concurrency or remote self-consumption systems will be greatly affected.

Concurrency factor

The simultaneity factor is defined as the ratio between the energy consumed and the energy generated during a given time interval.

Understanding the simultaneity factor requires analyzing the typical daily load curve of the consumer unit, which outlines the customer's consumption profile over a period of one day.

Figure 1 shows a load curve obtained from a simulation with the SOLergo software. The load curve shows the power being consumed by local loads at each moment of the day. The graph area, throughout the day, represents the energy that was consumed in that same period.

The two peaks of the curve in Figure 1 indicate periods in which there is greater energy consumption, which occurs between 6 and 8 am, the period when people are getting ready to work, and between 7 pm and 11 pm, which is the period when people get home and start using showers and appliances.

Figura 1 – Curva de carga de uma residência
Figure 1 – Load curve of a residence

Simulation of an installation with a low concurrency factor

Knowing the load curve of the residence and using the SOLergo software, it is possible to size a photovoltaic system to meet the energy needs of this consumer.

Figure 2 illustrates the load curve together with the generation curve of the sized photovoltaic system, obtained through simulation in SOLergo. Figure 3 presents the graphs generated by the SOLergo software itself with a summary of the energy generated and consumed annually by the consumer unit, from this database that the curves of the example presented were obtained.

It is possible to make some interesting analyzes regarding the consumption profile of this unit based on Figure 2.

During the period of highest generation (blue curve), low consumption is recorded (red curve), which is the period when residents are at work and few loads are used at home.

Figura 2 – Curvas de carga e de geração
Figure 2 – Load and generation curves

This fact means that the simultaneity factor is low, since most of the energy generated will not be used instantly, but injected into the distributor's network.

Figura 3 – Dados de energia gerada e consumida da unidade consumidora. Fonte: SOLergo
Figure 3 – Data on energy generated and consumed by the consumer unit. Source: SOLergo

The energy consumed simultaneously with generation is represented by the area painted in purple in Figure 4, which consists of the lower intersection of the two curves.

This area represents self-consumed energy, that is, the energy generated by the photovoltaic plant and consumed simultaneously by the local loads of the consumer unit.

Figura 4 – Energia autoconsumida em simultaneidade com a geração de energia
Figure 4 – Self-consumed energy simultaneously with energy generation

The green area in Figure 5 represents all the electrical energy generated by the photovoltaic system over a period of one day.

Calculation of the simultaneity factor

To calculate the simultaneity factor, simply divide the amount of self-consumed energy, represented by the purple area in Figure 4, by the total energy amount, represented by the green area in Figure 5.

In order for this division to be understood more clearly, this article will provide a numerical example after explaining the equations that represent the simultaneity factor.

Figura 5 – Energia total gerada pela usina em um dia
Figure 5 – Total energy generated by the plant in one day

The simultaneity factor is defined as the ratio between the energy consumed in the generation interval (self-consumed) and the total energy generated in the same interval, according to the following equation:

As previously stated, self-consumed energy corresponds to the fraction of the generated energy that is consumed simultaneously by the loads. Ideally, with a simultaneity factor of 100%, all energy generated by the photovoltaic system is consumed on site, with zero energy export. On the other hand, a low simultaneity factor indicates that little energy is consumed on site and most of the photovoltaic generation is exported.

The self-consumed energy in an installation can be calculated by the difference between the total energy generated recorded by the inverter (over a period of one month) and the injected energy that appears on the energy bill, both for the same period.

The equation that represents self-consumed energy is presented below:

Example of a real case

To illustrate, let's calculate the simultaneity factor for a real case, a residence equipped with a photovoltaic microgeneration system.

Firstly, we will calculate the self-consumed energy and to do this we need to collect the injected energy, which is data presented on the energy bill.

This energy corresponds to the surplus (everything that is not self-consumed) of energy injected into the concessionaire's distribution network. Figure 6 presents this data taken from the energy bill of the concessionaire CEMIG, in Minas Gerais.

Figura 6 – Leitura da energia injetada de uma fatura de energia
Figure 6 – Reading the energy injected from an energy bill

Once we have the injected energy (446 kWh), we simply take the total generation measured by the inverter to calculate the self-consumed energy.

The reading period for the injected energy was from 11/18/2022 to 12/20/2022, as shown in Figure 6. Therefore, the energy generated in that same period must be taken. To do this, the inverter monitoring is consulted, which presents daily generation data for this period, as shown in Figure 7.

Figura 7 – Monitoramento de geração do inversor para o período de 18/11/2022 a 20/12/2022. O eixo vertical corresponde à potência na saída do inversor (em kW). O eixo vertical corresponde ao tempo
Figure 7 – Inverter generation monitoring for the period from 11/18/2022 to 12/20/2022. The vertical axis corresponds to the power at the inverter output (in kW). The vertical axis corresponds to time

In the period from 11/18/2022 to 12/20/2022, according to the inverter monitoring system, the photovoltaic system provided 510 kWh of energy. This energy corresponds to the yellow area of the graph in Figure 7.

Knowing the energy generated, measured at the output of the inverter (510 kWh), and the energy injected into the bidirectional meter (446 kWh), taken from the energy bill, the self-consumed energy is calculated, which is:

Self-consumed energy=510-446=64 kWh

Thus, the simultaneity factor of this installation, calculated over a period of one month, is:

Simultaneity factor=64 / 510 = 12.55%

Conclusions

For the exampled residence, the simultaneity factor is 12.55%, which is a low value, which means that most of its energy (87.45%) is injected into the grid.

If this plant were included in the new law, there would be a higher bill payment due to Fio B, since each credit (kWh) injected that is compensated receives the charge from Fio B (percentage of Fio B according to the transition).

Therefore, projects will have a slower return on investment the lower the simultaneity factor.

For consumers such as supermarkets and industries, which have high consumption during generation periods, this factor tends to increase and can reach such high levels that the new rule will almost not interfere with the return on investment time, as long as the simultaneity factor be loud enough.

It is important to highlight that the calculations carried out in this article can only be obtained accurately in locations that already have a photovoltaic plant installed, as data such as the total energy generated and the energy injected are required.

However, for new proposals, this data is not available. So, what to do in these cases?

The most reliable way to obtain this simultaneity factor would be to raise the customer's load curve and compare it with the predicted generation curve (by simulation) of the sized photovoltaic plant. Thus, a comparison can be made between these two curves and the simultaneity factor can be raised.

As surveying the load curve is a time-consuming process, an alternative is to use simultaneity factor values from plants already installed at customers of the same type.

Thus, to prepare a new proposal, the consumption profile of the customer to be served is compared with the profile of another customer already cataloged and the simultaneity factor is used to calculate the return on investment time.

Another alternative is to use software such as SOLergo, which makes it possible to create the customer's load curve based on knowledge of their installed load. The software also calculates the simultaneity factor and delivers the entire economic analysis considering law 14,300.

Bibliographic references

[1] Badra, Matthew. Simultaneity factor will be key to GD's accelerated growth. Solar Channel. Campinas January 19, 2022. Available at: . Accessed on: 01/15/2022.

[2] Energês Team. Title: Simultaneity impacts the viability of own generation?. Energês, March 10, 2022. Available at: . Accessed January 15, 2023.


The opinions and information expressed are the sole responsibility of the author and do not necessarily represent the official position of Canal Solar.

Picture of Geraldo Silveira
Geraldo Silveira
PhD student and Master in Electrical Engineering from UFMG (Federal University of Minas Gerais). Graduated in Electrical Engineering from UNIFEI (Federal University of Itajubá). He is a specialist in photovoltaic solar energy, working in the design, execution and evaluation of solar plants. He is enthusiastic about electrical energy systems and short circuit studies.

8 Responses

  1. Para alcançar uma precisão significativamente maior, deve-se usar uma curva de carga para uma semana ou um mês, já que ela costuma variar conforme dia da semana. Da mesma forma, não basta um dia aleatório de irradiação (curva azul), mas deve-se calcular com dados climáticos de um ano inteiro: temos dias de sol, de nuvens, de chuva etc.
    Isso mostra a restrição do Solergo no cálculo, porque ele faz um cálculo com média mensal. Outros programas, como PV*SOL e PVsyst calculam em intervalo de hora ou de minuto ao longo do ano.

  2. Regarding charging, the question is whether the value of wire b is charged when injected into the network or when the kW balance is used????

  3. Good afternoon Professor, very good text! I'm going to show two salespeople that I have at the company, I'm also in sales. Do you happen to have any simulation of light and or Enel?

  4. Congratulations Doctor Geraldo for the article, it was extremely important as it clarified points that were quite nebulous. Hug.

Leave a Reply

Your email address will not be published. Required fields are marked *

Receive the latest news

Subscribe to our weekly newsletter